◆ Paké Kaayaan
1.Ambient hawa: -30 ℃ ~ + 60 ℃;
2.Altitude: ≤3000m;
3.Laju angin: ≤34m / s;
4.Polusi kelas: ≤IV.
5.Storage hawa: -40 ℃ ~ + 85 ℃.
◆ Parameter Téknis Utama
NO. | Barang | Unit | Nilai |
1 | tegangan dipeunteun | kV | 40.5 |
2 | Frékuénsi kakuatan 1min tahan tegangan | kV | 95 |
3 | dorongan kilat tahan tegangan | kV | 185 |
4 | frékuénsi dipeunteun | Hz | 50 |
5 | dipeunteun ayeuna | A | 630.1250.1600 |
6 | dipeunteun pondok circuit megatkeun arus | kA | 20, 25, 31,5 |
7 | dipeunteun sirkuit pondok nyieun arus (puncak) | kA | 50, 63, 80 |
8 | dipeunteun puncak tahan ayeuna | kA | 50, 63, 80 |
9 | 4s tahan ayeuna | kA | 20, 25, 31,5 |
10 | dipeunteun runtuyan operasi | S | O-0.1s-CO-3s-CO-6S-60s recovery |
11 | dipeunteun short circuit ayeuna megatkeun angka | kali | 30 |
12 | hirup mékanis | kali | 10000 |
13 | tegangan kontrol mékanisme | DI | AC/DC220 |
14 | sirkuit sekundér 1mnt frékuénsi kakuatan tahan tegangan | kV | 2 |
15 | jarak clearance antara kontak kabuka | mm | 16±1 |
16 | leuwih perjalanan | mm | 4±0,5 |
17 | laju muka | Ibu | 1.4-1.8 |
18 | laju nutup | Ibu | 0.4-0.8 |
19 | kontak nutup waktos mumbul | Ibu | ≤5 |
20 | tilu fase bubuka / nutup Asynchronism | Ibu | ≤2 |
dua puluh hiji | waktos nutup | Ibu | ≤100 |
duapuluh dua | waktos muka | Ibu | ≤50 |
dua puluh tilu | beurat | kg | 270 |
◆Gemblengna Ngagambar