Pursuits langgeng kami nyaéta sikep "nganggap pasar, nganggap adat, nganggap elmu" kitu ogé téori "kualitas dasar, yakin dina 1st jeung manajemén canggih" pikeun Vs1 12kv tarik kaluar tipe Vcb pikeun tegangan High. Ngalihkeun 10kvJero rohangan Hv vakum Circuit breakerMékanisme Operasi di Switchgear, Kami ngabagéakeun para klién, asosiasi perusahaan sareng pals ti sakumna bumi pikeun ngahubungi kami sareng milarian gawé babarengan pikeun kauntungan tambahan.
Pursuits langgeng urang téh sikep "nganggap pasar, nganggap adat, hal elmu" ogé téori "kualitas dasar, percanten ka 1st jeung manajemén nu maju" pikeun12kv circuit breaker vakum,12kv vsg vcb,Cina Vsg 12kv,Tegangan tinggi Jero rohangan vakum Circuit breaker,Pameungpeuk jero rohangan,Jero rohangan Circuit breaker,Jero rohangan High tegangan vakum breaker,Jero rohangan Hv vakum Circuit breaker,VCB jero rohangan,Vcb jero rohangan,Tilu Fase Hv Jero rohangan Circuit Breaker,vakum Circuit breaker,vakum Circuit breaker 12kv jero rohangan , Loba rupa solusi béda sadia pikeun anjeun milih, anjeun tiasa ngalakukeun hiji-eureun balanja di dieu. Jeung pesenan ngaropéa nu bisa ditarima. Usaha nyata pikeun kéngingkeun kaayaan win-win, upami mungkin, kami hoyong nganteurkeun langkung seueur dukungan pikeun para nasabah. Wilujeng sumping sadayana pembeli anu saé komunikasi detil solusi sareng kami !!
VSG-12 indoor HV vakum circuit breaker mangrupakeun 3-fase AC 50Hz 12kV parabot switch indoor.
♦ cara Instalasi: tipe withdrawable, tipe dibereskeun;
♦ mékanisme operasi: mékanisme operasi spring;
♦ tipe kutub: kutub dirakit, kutub study;
♦ Jarak fase-ka-fase: 150mm, 210mm, 275mm;
Kaayaan Lingkungan
♦ hawa ambient: -15r ~ + 40r;
♦ Luhurna:
♦ Kalembaban relatif: rata-rata poean ;
♦ Inténsitas gempa:
♦ Tempat tanpa seuneu, bahya ledakan, kotor serius, korosi kimiawi, kitu ogé Geter sengit.
Parameter Téknis Utama
No | Barang | Unit | Nilai |
1 | tegangan dipeunteun | kV | 12 |
2 | 1 mnt frékuénsi kakuatan tahan tegangan | 42 | |
3 | Dipeunteun kilat dorongan tahan tegangan | 75 | |
4 | Frékuénsi dipeunteun | Hz | 50 |
5 | Dipeunteun ayeuna | A | 630, 1250, 1600, 2000, 2500, 3150 |
6 | Dipeunteun pondok circuit megatkeun arus | kA | 25, 31,5, 40 |
7 | Dipeunteun waktos pondok tahan ayeuna | 25, 31,5, 40 | |
8 | Dipeunteun durasi sirkuit pondok | s | 4 |
9 | Nilai puncak dipeunteun tahan ayeuna | kA | 63, 80, 100 |
10 | Dipeunteun pondok circuit nyieun ayeuna | 63, 80, 100 | |
11 | Frékuénsi kakuatan sirkuit sekundér tahan tegangan (Imin) | DI | 2000 |
12 | Dipeunteun single / back-to-back kapasitor bank megatkeun ayeuna | A | 630/400 (800/400 pikeun 40kA) |
Waktu muka (tegangan dipeunteun) | Ibu | 20-50 | |
14 | Waktu nutup (tegangan dipeunteun) | Ibu | 35-70 |
15 | Kahirupan mékanis | Kali | 10000 |
16 | Kahirupan listrik | Kelas E2 | |
17 | Pindah jeung tetep kontak kumulatif diwenangkeun maké ketebalan | mm | 3 |
18 | Dipeunteun tegangan operasi nutup | DI | AC/DC110/220 |
19 | Dipeunteun tegangan operasi bukaan |
No | Barang | Unit | Nilai |
20 | Motor dipeunteun kakuatan | DI | 90 |
dua puluh hiji | waktos ngecas | s | ≤15 |
duapuluh dua | Clearance antara kontak kabuka | mm | 9±1 |
dua puluh tilu | Leuwih perjalanan | mm | 3±1 |
dua puluh opat | Kontak nutup waktos mumbul | Ibu | ≤2 |
25 | Tilu fase bubuka sareng nutup asynchronism | Ibu | ≤2 |
26 | Rata laju muka | Ibu | 0.9-1.7 |
27 | Laju nutup rata | Ibu | 0.6~1.0 |
28 | lalawanan circuit conductive utama | mΩ | ≤45 (630A) ≤35(1250-2000A) ≤25 (di luhur 2500A) |
29 | Tekanan nutup kontak tina kontak | N | 3100-3700 (25-31.5kA) 4400-4800 (40kA) |
30 | Dipeunteun runtuyan operasi | O-0.3s-CO-180s-CO |
Catetan: lamun ayeuna 4000A, perlu cooling hawa kapaksa.
Gambar Struktur Umum sareng Ukuran Pamasangan (unit: mm)
♦Jenis tarik kaluar (tiang dirakit)
lega kabinét | dipeunteun ayeuna (A) | dipeunteun pondok circuit megatkeun arus (kA) | P | H | A | B | C | D | AND | F | G | J | K | L | M | N | R | S | T |
650 | 630 | 20'31.5 | 150 | 275 | 490 | 502 | 492 | 500 | 433 | 626 | 035 | 280 | 598 | 76 | 78 | 637 | 501 | 202 | 40 |
650 | 12j0 | 20-31.5 | 150 | 275 | 490 | 502 | 492 | 500 | 433 | 626 | 049 | 280 | 598 | 76 | 78 | 637 | 501 | 202 | 40 |
800 | 630 | 20-31.5 | 210 | 275 | 638 | 652 | 640 | 650 | 433 | 626 | 035 | 280 | 598 | 76 | 78 | 637 | 501 | 277 | 40 |
800 | 1250 | 20-40 | 210 | 275 | 638 | 652 | 640 | 650 | 433 | 626 | 049 | 280 | 598 | 76 | 78 | 637 | 501 | 277 | 40 |
800 | 1600 | 31.5-40 | 210 | 275 | 638 | 652 | 640 | 650 | 433 | 626 | 055 | 280 | 598 | 76 | 78 | 637 | 501 | 277 | 40 |
WOO | 030 | 20-31.5 | 275 | 275 | 838 | 852 | 838 | 850 | 433 | 626 | 035 | 280 | 598 | 76 | 78 | 637 | 501 | 377 | 40 |
1000 | 1250 | 20-40 | 275 | 275 | 838 | 852 | 838 | 850 | 433 | 626 | 049 | 280 | 598 | 76 | 78 | 637 | 501 | 377 | 40 |
1000 | 1600 | 31.5-40 | 275 | 275 | 838 | 852 | 838 | 850 | 433 | 626 | 055 | 280 | 598 | 76 | 78 | 637 | 501 | 377 | 40 |
1000 | 1600-2000 | 31.5-40 | 310 | 310 | 838 | 852 | 838 | 850 | 361 | 680 | 079 | 295 | 586 | 77 | 88 | 698 | 529 | 377 | 0 |
1000 | 2500-4000 | 31.5-40 | 310 | 310 | 838 | 852 | 838 | 850 | 361 | 680 | 0109 | 295 | 586 | 77 | 88 | 698 | 529 | 377 | 0 |
♦ Jenis tarik kaluar (kutub dipasang)
G | J | K | L | M | N | R | S | T |
0)35 | 280 | 598 | 76 | 78 | 637 | 501 | 202 | 40 |
①49 | 280 | 598 | 76 | 78 | 637 | 501 | 202 | 40 |
035 | 280 | 598 | 76 | 78 | 637 | 501 | 277 | 40 |
①49 | 280 | 598 | 76 | 78 | 637 | 501 | 277 | 40 |
(D79 | 295 | 586 | 77 | 88 | 698 | 509 | 377 | 0 |
0109 | 295 | 586 | 77 | 88 | 698 | 509 | 377 | 0 |
♦Tipe tetep (tiang dirakit)
A | B | C | AND | F | G1 G2 | J | K |
520 | 520 | 588 | 580 | 72 | abdi | 237 | 462 |
720 | 720 | 770 | 580 | 72 | abdi | 237 | 462 |
650 | 720 | 770 | 632 | 85 | II | 252 | 472 |
♦ Tipe tetep (kutub dipasang)
Pursuits langgeng urang téh sikep "nganggap pasar, nganggap adat, nganggap elmu" kitu ogé téori "kualitas nu dasar, yakin dina 1st jeung manajemén canggih" pikeun harga Wajar Vs1 12kv Tipe Handcart Vcb pikeun High. Saklar tegangan 10kvJero rohangan Hvvakum Circuit breakerMékanisme Operasi di Switchgear, Kami ngabagéakeun para klién, asosiasi perusahaan sareng pals ti sakumna bumi pikeun ngahubungi kami sareng milarian gawé babarengan pikeun kauntungan tambahan.
harga lumrah Cina Vsg-12kv / 24kv, Loba rupa solusi béda sadia pikeun anjeun milih, anjeun tiasa ngalakukeun hiji-eureun balanja di dieu. Jeung pesenan ngaropéa nu bisa ditarima. Usaha nyata pikeun kéngingkeun kaayaan win-win, upami mungkin, kami hoyong nganteurkeun langkung seueur dukungan pikeun para nasabah. Wilujeng sumping sadayana pembeli anu saé komunikasi detil solusi sareng kami !!
VSG-12 indoor HV vakum circuit breaker mangrupakeun 3-fase
AC 50Hz 12kV parabot switch indoor.
♦ cara Instalasi: tipe withdrawable, tipe dibereskeun;
♦ mékanisme operasi: mékanisme operasi spring;
♦ tipe kutub: kutub dirakit, kutub study;
♦ Jarak fase-ka-fase: 150mm, 210mm, 275mm;