ZN12-12 / 40.5 indoor HV vakum circuit breaker mangrupakeun 3-fase AC 50Hz 12kV / 40.5KV parabot switch indoor.
♦ cara Instalasi: tipe withdrawable, tipe dibereskeun;
♦ mékanisme operasi: spring ope mékanisme rating;
♦ Aplikasi: switchgear GBC-35, JYN1-35.
Kaayaan Lingkungan
♦ Suhu ambient: -25 ° C ~ + 40 ° C;
♦ Luhurna:
♦ Kalembaban relatif: rata-rata poean ;
♦ Inténsitas gempa:
♦ Tempat tanpa seuneu, bahya ledakan, kotor serius, korosi kimiawi, kitu ogé Geter sengit.
Parameter Téknis Utama
ZN12-12
No | Barang | Unit | Nilai | ||||
1 | tegangan dipeunteun | kV | |||||
2 | Dipeunteun ayeuna | A | 630, 1250, 1600 | 1250, 1600,2000, 2500.3150 | 2000, 2500, 3150.4000 | ||
3 | Dipeunteun pondok circuit megatkeun arus | kA | 20 | 25 | 31.5 | 40 | 50 |
4 | Arus stabilitas dinamis (puncak) | kA | 50 | 63 | 80 | 100 | 125 |
5 | 4s ayeuna stabilitas termal | kA | 20 | 25 | 31.5 | 40/3s | 50/3s |
6 | Dipeunteun pondok circuit nyieun ayeuna | kA | 50 | 63 | 80 | 100 | 125 |
7 | Nomer pegatna arus sirkuit pondok | kali | 30 | 12 | |||
8 | Dipeunteun runtuyan operasi | CO-0.3S-CO-180S-CO | O-180S-CO-180S-CO | ||||
9 | Kahirupan mékanis | kali | 10000 | 6000 | |||
10 | Dipeunteun angka megatkeun ayeuna | kali | 10000 | 6000 | |||
11 | Impuls kilat dipeunteun tahan tegangan (gelombang pinuh) | kV | 75 | ||||
12 | Frékuénsi kakuatan waktos pondok dipeunteun tahan ayeuna (1 mnt) | kV | 42 | ||||
13 | waktos nutup | Ibu | ≤75 | ||||
14 | Waktu muka | Ibu | ≤65 | ||||
15 | Daya sareng tegangan dipeunteun tina motor panyimpen énergi | W/V | 275W/ 110V, 220V | ||||
16 | waktos neundeun énergi | s |
|
No | Barang | Unit | Nilai |
17 | Tegangan dipeunteun tina coil nutup | DI | 110V, 220V |
18 | Tegangan dipeunteun tina bukaan coil | DI | |
19 | Tegangan dipeunteun tina coil interlock | DI | |
20 | Dipeunteun ayeuna release | A | 5 |
dua puluh hiji | Dipeunteun ayeuna saklar bantu | A | AC10A, DC5A |
ZN12-40.5
No | Barang | Unit | Nilai | |
1 | tegangan dipeunteun | kV | 40.5 | |
2 | Dipeunteun ayeuna | A | 1250, 1600, 2000 | 1250, 1600,2000,2500 |
3 | Dipeunteun pondok circuit megatkeun arus | kA | 20, 25 | 31.5 |
4 | Arus stabilitas dinamis (puncak) | kA | 50, 63 | 80 |
5 | 4s ayeuna stabilitas termal | kA | 20, 25 | 31.5 |
6 | Dipeunteun sirkuit pondok nyieun arus (puncak) | kA | 50, 63 | 80 |
7 | Nomer pegatna arus sirkuit pondok | kali | 30 | 20 |
8 | Dipeunteun runtuyan operasi | CO-0.3S-CO-180S-CO | ||
9 | Dipeunteun dorongan kilat tahan tegangan (gelombang pinuh) | kV | 180 | |
10 | Frékuénsi kakuatan waktos pondok dipeunteun tahan ayeuna (1 mnt) | kV | 95 | |
11 | waktos nutup | Ibu | ≤90 | |
12 | Waktu muka | Ibu | ≤75 | |
13 | Mékanika! hirup | kali | 10000 | 60000 |
14 | Dipeunteun angka megatkeun ayeuna | kali | 10000 | 60000 |
15 | Dipeunteun kapasitor bank megatkeun ayeuna | A | 630 | |
Kakuatan motor neundeun énergi | DI | 275 | ||
17 | Tegangan dipeunteun tina motor neundeun énergi | DI | ≃110V, 220V | |
18 | waktos neundeun énergi | s | ≤15 | |
19 | Tegangan dipeunteun tina nutup sareng bukaan coil | DI | ≃110V, 220V | |
20 | Dipeunteun ayeuna kaluaran overcurrent | A | 5 | |
dua puluh hiji | Dipeunteun ayeuna switch bantu | A | AC10A, DC5A |
Gambar Struktur Umum sareng Ukuran Pamasangan (unit: mm)
♦ZN12-12 (dipasang condong)
Catetan: Diménsi 360mm kanggo ayeuna di luhur 2000A, handapeun 2000A, dimensina 350mm.
Catetan, dina gambar, (215) hartina lamun L3 = 516mm, dimensi na 215mm.
Dina 1600A: luhur jeung handap outlet terminal liang 2-M12
Luhur 2000A: luhur jeung handap outlet terminal liang 4-M12
Tipe | L | L1 | L2 | L3 | Katerangan |
ZN12-12 | 210 | 586 | 610 | 516 | Kalayan partisi antar-fase |
230 | 620 | 650 | 565 | ||
250 | 700 | 740 | 565 | ||
275 | 696 | 720 | 516 |
♦ZN12-12B (siram dipasang)(569575)
Catetan: (575) jeung (364) hartina mun sirkuit pondok megatkeun ayeuna 40kA atawa saluhureuna, dimensi na 575mm, 364mm.
Luhur jeung handap outlet terminal liang 4-M12
Catetan: (215) hartina lamun L3=516mm;dimensi na nyaeta 215 mm.
Tipe | L | L1 | L2 | L3 |
ZN12-12B | 210 | 586 | 610 | 516 |
230 | 620 | 650 | 565 | |
250 | 700 | 740 | 565 | |
275 | 696 | 720 | 516 |
Katerangan Jeung partisi antar-fase